The CG.EM series comprises Ex db, Ex eb and Ex tb certified metal cable glands for non-armored, shielded EMC cables. Made from brass nickel plated or AISI 316 stainless steel. Metric and NPT versions available.
Suitable for operation in Zone 1, Zone 2, Zone 21 and Zone 22
Suitable for operation in Class I, Zone 1/2/22
Suitable for operation in Class I, Division 2 when installed in accordance with NEC501.10(B)(2)
Degree of protection IP66 / IP68, UL Type 4X
The metal cable glands type CG.EM can be used indoor and outdoor in Zone 1, Zone 2, Zone 21 and Zone 22 hazardous areas.
They are intended to be used with shielded cables where the shield will be connected to the inner shielding ring of the gland in order to provide the necessary EMC protection.
Example: CG.EM.M20.BN.C.18.K01
Cable gland metal, for shielded EMC cables, thread size M20, body brass nickel-plated, chloroprene seals for -40 °C ... 80 °C, installation thread length 18 mm, one piece